Higher yields / Safe & Reliable / Smart / User-friendly
2 MPP trackers, Max. effificiency up to 98.5%
Zero export application, VSG application
String intelligent monitoring (optional)
Wide output voltage range
Anti-PID function (Optional)
- Model SUN-4K-G06P3-EU-AM2-P1 SUN-5K-G06P3-EU-AM2-P1 SUN-6K-G06P3-EU-AM2-P1 SUN-7K-G06P3-EU-AM2-P1 SUN-8K-G06P3-EU-AM2-P1 SUN-9K-G06P3-EU-AM2-P1 SUN-10K-G06P3-EU-AM2-P1 SUN-12K-G06P3-EU-AM2-P1 SUN-15K-G06P3-EU-AM2-P1
- PV String Input Date Max. PV Input Power(kW) 5.2 6.5 7.8 9.1 10.4 11.7 13 15.6 19.5
- Max. PV Input Voltage(V) 1100
- Start-up Voltage(V) 140
- MPPT voltage range(V) 120-1000
- Rated PV Input voltage(V) 600
- Max. Input Short Circuit Current (A) 30+30 30+39
- Max. Operating PV Input Current(A) 20+20 20+26
- No. of MPP Trackers/No. of Strings per MPP Tracker 2/1+1 2/1+2
- AC Input/Output Side Rated AC Output Active Power(kW) 4 5 6 7 8 9 10 12 15
- Max. AC Output Apparent Power(kVA) 4.4 5.5 6.6 7.7 8.8 9.9 11 13.2 16.5
- Rated AC output current (A) 6.1/5.8 7.6/7.3 9.1/8.7 10.7/10.2 12.2/11.6 13.7/13.1 15.2/14.5 18.2/17.4 22.8/21.8
- Max. AC Output Current(A) 6.7/6.4 8.4/8 10/9.6 11.7/11.2 13.4/12.8 15/14.4 16.7/16 20/19.2 25/24
- Rated output voltage/range (V) 220/380V, 230/400V 0.85Un-1.1Un Grid Connection Form 3L/N/PE
- Rated Output Grid Frequency/range(Hz) 50/45-55, 60/55-65
- Power Factor Adjustment Range 0.8 leading to 0.8lagging
- Total Current Harmonic Distortion THDi <3% DC Injection Current <0.5%ln
- Efficiency Max. Efficiency 98.1% 98.2% 98.3% 98.5%
- Euro Efficiency 97.5% 97.6% 97.8% 98.0%
- MPPT Efficiency >99%
- Equipment Protection DC Polarity Reverse Connection Protection yes
- AC Output Overcurrent Protection yes
- AC Output Overvoltage Protection yes
- AC Output Short Circuit Protection yes
- Thermal Protection yes
- DC Terminal Insulation Impedance Monitoring yes
- DC Component Monitoring yes
- Ground Fault Current Monitoring yes
- Power Network Monitoring yes
- sland Protection Monitoring yes
- Earth Fault Detection yes
- DC Input Switch yes
- Overvoltage Load Drop Protection yes
- Residual Current (RCD) Detection yes
- Surge Protection Level TYPE II(DC),TYPE II(AC) Interface
- Communication Interface RS485/RS232 /WiFi/LAN
- General Data Operating Temperature Range (°C) -25 to +60℃, >45℃
- Derating Permissible Ambient Humidity 0~100%
- Permissible Altitude (m) 4000m Noise (dB) <45 dB(A)
- Ingress Protection(IP) Rating IP 65 Inverter Topology
- Non-Isolated Over Voltage Category OVC II(DC),OVC III(AC)
- Cabinet Size (WxHxD mm) 283mm*463mm*178mm(Excluding connectors and brackets)
- Weight [kg] 11
- Warranty [year] 5 years
- Type Of Cooling natural cooling
- Intelligent air cooling Grid Regulation IEC 61727,IEC 62116,EN 50549
- Safety EMC/Standard IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2